The Trane Precedent WHC102H3,4,W is a high-efficiency 8.5 ton packaged heat pump with a variable-speed direct-drive blower.

Hub Highlights:
  • Heating: 12 EER, 15.5 IEER, 3.63 high-heating COP
  • Capacity: 105,900 Btu/h cooling capacity and 93,000 Btu/h high-heating capacity
  • Compressor Type: 2 Scroll compressors
  • Electric Heat Up: Optional electric heat up to 36 kW

The Carrier WeatherMaster 50HCQD07 1-Speed is a high-efficiency 6 ton packaged heat pump with two-stage cooling and a single-speed indoor fan.

Hub Highlights:
  • Heating: 12 EER, 14 IEER, 3.4 high-heating COP
  • Capacity: 70,000 Btu/h cooling capacity and 69,000 Btu/h high-heating capacity
  • Compressor Type: 2-stage scroll compressor
  • Electric Heat Up: Optional electric heat up to 28 kW

The Carrier WeatherMaster 50HCQA06 is a high-efficiency 5 ton packaged heat pump with single-stage cooling.

Hub Highlights:
  • Heating: 11.7 EER, 15 SEER, 8.2 HSPF
  • Capacity: 58,500 Btu/h cooling capacity and 55,000 Btu/h high-heating capacity
  • Compressor Type: 1-stage scroll compressor
  • Electric Heat Up: Optional electric heat up to 26.5 kW

The Carrier WeatherMaster 50HCQA05 is a high-efficiency 4 ton packaged heat pump with single-stage cooling.

Hub Highlights:
  • Heating: 12.8 EER, 15.8 SEER, 8.1 HSPF
  • Capacity: 47,000 Btu/h cooling capacity and 46,000 Btu/h high-heating capacity
  • Compressor Type: Scroll
  • Electric Heat Up: Optional electric heat up to 23 kW

The Trane Precedent WHC120H3,4,W is a high-efficiency 10 ton packaged heat pump with a variable-speed direct-drive blower.

Hub Highlights:
  • Heating: 11.5 EER, 15.5 IEER, 3.63 high-heating COP
  • Capacity: 123,600 Btu/h cooling capacity and 118,000 Btu/h high-heating capacity
  • Compressor Type: 2 Scroll compressors
  • Electric Heat Up: Optional electric heat up to 54 kW

The Carrier WeatherMaster 50HCQA04 is a high-efficiency 3 ton packaged heat pump with single-stage cooling.

Hub Highlights:
  • Heating: 12.7 EER, 15.6 SEER, 8 HSPF
  • Capacity: 36,400 Btu/h cooling capacity and 34,000 Btu/h high-heating capacity
  • Compressor Type: Scroll
  • Electric Heat Up: Optional electric heat up to 16 kW

Ventilation system controller with economizer and CO2-based demand control ventilation capabilities. The device may be configured and monitored wirelessly with XCSpec’s Mini Access Point.

Hub Highlights:
  • LED status indicators, information and commissioning available through integrated WiFi.
  • WiFi connection but no supported building management system (BMS) protocols.
  • Poor performance under Hub simulated occupancy profiles.

Ventilation system controller with economizer and CO2-based demand control ventilation (DCV) capabilities. The device may be configured and monitored wirelessly with Pelican’s Connect web-app. The controller performance was tested at Pelican’s recommended setting of 800 PPM and at 1000 PPM.

Hub Highlights:
  • No on-board display, device configuration and monitoring through Pelican Connect web-app.
  • Proprietary three wire data connection to a Pelican thermostat to access wireless connection to gateway.
  •  Integrates with other building automation systems using Pelican’s application programming interface (API).
  • Good performance under Hub simulated occupancy profiles at recommended setting.
  • Cloud-based controls enable seamless software updates to connected devices

Ventilation system controller with economizer and CO2-based demand control ventilation capabilities. The device may be configured locally or with wired communication protocols.

Hub Highlights:
  • Color touchscreen display.
  • BACnet MS/TP supported.
  • Good performance under Hub simulated occupancy profiles.
  • Also functions as a thermostat.
  • Economizer Control Options Single dry bulb change over; Single enthalpy change over; Differential enthalpy change over

Ventilation controller with economizer with available inputs for CO2-based demand control ventilation capabilities.

Hub Highlights:
  • Monochrome LCD display and buttons for commissioning, troubleshooting, or viewing status.
  • BACnet MS/TP supported.
  • Good performance under Hub simulated occupancy profiles.
  • CO2 Sensor Compatibility Universal – Works with any CO2 sensor that has the ability to output compatible signal

Ventilation controller with economizer with available inputs for CO2-based demand control ventilation capabilities. Using Honeywell Sulk Bus enabled sensors enables more fault detection features. Two configurations were evaluated (fast and slow).

Hub Highlights:
  • Monochrome LCD display and buttons for commissioning, troubleshooting, or viewing status.
  • No direct connection to building management system.
  • Great performance under Hub simulated occupancy profiles.
  • Purchasing a USB adapter allows PC based commissioning software to be used. This will allow the user to choose a "fast" mode which performed better in Hub testing protocols.

Ventilation controller with economizer with available inputs for CO2-based demand control ventilation capabilities. Using Honeywell Sulk Bus enabled sensors enables more fault detection features. Two configurations were evaluated (fast and slow).

Hub Highlights:
  • Monochrome LCD display and buttons for commissioning, troubleshooting, or viewing status.
  • No direct connection to building management system.
  • Great performance under Hub simulated occupancy profiles.
  • Purchasing a USB adapter allows PC based commissioning software to be used. This will allow the user to choose a "fast" mode which performed better in Hub testing protocols.
  • Controller CO2 Sensor Input Signal Types 2-10 VDC, 0-2000 ppm Analog or Sylk bus TR40 CO2 sensor

Ventilation system controller with economizer and CO2-based demand control ventilation (DCV) capabilities. The device may be configured and monitored wirelessly with Pelican’s Connect web-app. The controller performance was tested at Pelican’s recommended setting of 800 PPM and at 1000 PPM.

Hub Highlights:
  • No on-board display, device configuration and monitoring through Pelican Connect web-app.
  • Proprietary three wire data connection to a Pelican thermostat to access wireless connection to gateway.
  •  Integrates with other building automation systems using Pelican’s application programming interface (API).
  • Good performance under Hub simulated occupancy profiles at recommended setting.
  • Cloud-based controls enable seamless software updates to connected devices

Ventilation controller with economizer with modular upgrade to allow for CO2-based demand control ventilation capabilities.

Hub Highlights:
  • Monochrome LCD display and buttons for commissioning, troubleshooting, or viewing status.
  • Optional module available for BACnet MS/TP communication.
  • Good performance under Hub simulated occupancy profiles.
  • Modular expansions available.

Thermostat that measures, carbon dioxide, temperature, and humidity (TS250H) that can be used for long-term monitoring and demand control ventilation. The carbon dioxide sensor is optional.

Hub Highlights:
  • Does not display CO2 value on device. Display of CO2 value available on web-portal or app for authorized users
  • Pelican's Connect web-app displays historical data via graphs and has configurable alarms. Free access to Pelican Connect web-app for basic system operation. Additional features available with low-cost subscription.
  • Excellent performance on Hub CO2 accuracy testing protocols
  • Integrates with other building automation systems using Pelican’s application programming interface (API). Requires an internet connection for the gateway.

Indoor air quality monitoring platform with CO2 sensors that has a web-based dashboard for long-term monitoring.

Hub Highlights:
  • CO2 value displayed on device and mobile app
  • Easily connected to any building automation system for monitoring or ventilation control
  • Good performance on Hub CO2 accuracy testing protocols
  • Includes CO2, temperature, humidity, particulate matter, ozone, and other sensors

Thermostat with integrated CO2 sensor for long term monitoring and demand control ventilation. The CO2 sensor is optional.

Hub Highlights:
  • Configurable display which can show values of CO2, temperature, humidity, and HVAC operating mode
  • Easily connected to any building automation system for monitoring or ventilation control
  • Good performance on Hub CO2 accuracy testing protocols
  • Includes temperature, humidity, and occupancy sensors

Carbon dioxide sensor for long term monitoring and demand control ventilation.

Hub Highlights:
  • Three color LEDs indicate CO2 range. Display of CO2 value publicly accessible through mobile app
  • Easily connected to any building automation system for monitoring or ventilation control
  • Excellent performance on Hub CO2 accuracy testing protocols
  • Includes temperature and humidity sensors

Indoor air quality monitoring platform with CO2 sensors that has a web-based dashboard for long-term monitoring.

Hub Highlights:
  • Basic display of CO2 and temperature values
  • No building automation system connection. Web-based software displays historical data via graphs and has configurable alarms
  • Excellent performance on Hub CO2 accuracy testing protocols
  • Includes temperature, humidity, and pressure sensors. Requires Wi-Fi connectivity to view and configure devices

Indoor air quality monitoring platform with CO2 sensors that has a customizable web-based dashboard for long-term monitoring.

Hub Highlights:
  • No display on device. Display of CO2 value only available through web-portal which can be publicly accessible
  • Can connect to building automation system through Siemens Connect ecosystem
  • Excellent performance on Hub CO2 accuracy testing protocols
  • Optional sensors include CO2, temperature, humidity, particulate matter, ozone, and others

Thermostat with integrated CO2 sensor for long term monitoring and demand control ventilation. The CO2 sensor is optional.

Hub Highlights:
  • Configurable display which can show values of CO2, temperature, humidity, and HVAC operating mode
  • Requires a controller and specialized training on Alerton's configuration environment to operate or connect to a building automation system
  • Excellent performance on Hub CO2 accuracy testing protocols
  • Includes temperature and humidity sensors. Can output sensor values through a connected controller

Carbon dioxide sensor for long term monitoring and demand control ventilation.

Hub Highlights:
  • Basic display of CO2 value, temperature, and humidity (optional)
  • Easily connected to any building automation system for monitoring or ventilation control. Both analog outputs and Modbus available
  • Excellent performance on Hub CO2 accuracy testing protocols
  • Includes temperature and humidity (optional) sensors and outputs

Carbon dioxide sensor for long term monitoring and demand control ventilation.

Hub Highlights:
  • Configurable display including color coded alerts based on CO2 value and other parameters
  • Easily connected to any building automation system for monitoring or ventilation control. Both analog outputs and Modbus available
  • Good performance on Hub CO2 accuracy testing protocols
  • Includes temperature and humidity sensors. Can view historical charts directly on the device