Daikin DRH072
Air-source heat pumps (ASHPs) are all-electric building heating and cooling solutions that use electrical energy to move (not convert) thermal energy from a source to a sink, where the source is the outdoors in the winter and indoors in the summer. An ASHP thus pumps heat in the opposite direction from which it would normally move.
Learn MoreIf you are experiencing issues with the comparison tool, please disable your adblocker.
Daikin DRH072
The Daikin DRH072 is a high-efficiency 6 ton packaged heat pump with a direct-drive blower.
Hub Highlights:
- Heating: 11.5 EER, 17 IEER, 3.4 high-heating COP
- Capacity: 69,000 Btu/h cooling capacity and 61,000 Btu/h high-heating capacity
- Compressor Type: 2-stage scroll compressor
- Electric Heat Up: Optional electric heat up to 30 kW
Last Edited on: Sep 20, 2022
Model Number | DRH072 |
Cooling Capacity (Btu/h) | 69,000 |
Cooling Efficiency: IEER | 17 |
Cooling Efficiency: SEER | Not reported |
Cooling Efficiency: EER | 11.5 |
Heating Capacity: High (Btu/h) | 61,000 |
Heating Capacity: Low (Btu/h) | 33,000 |
Heating Efficiency: High COP | 3.4 |
Heating Efficiency: Low COP | 2.25 |
Heating Efficiency: HSPF | Not reported |
Airflow (CFM) | 2200 |
Refrigerant | R-410A |
Sound Rating | 81 dBA |
Electric Heating Options | 5 kW, 10 kW, 15 kW, 20 kW, 30 kW |
Last Edited on: Aug 19, 2022
Nominal Input Voltage (V) | 460 |
Sample Size | 1 |
Rated Cooling Integrated Energy Efficiency Ratio (IEER)
|
17.0 |
Measured Cooling Integrated Energy Efficiency Ratio (IEER)
|
16.3 |
Measured IEER Bias from Rating
|
4% below rating |
Rated High-Heating Coefficient of Performance (COP)
|
3.4 |
Measured High-Heating Coefficient of Performance (COP)
|
3.5 |
Measured COP Bias from Rating
|
3% above rating |