Nidec
Replacing older motors in air handlers, pumps, and similar applications with highly efficient motors can save energy costs and improve equipment reliability.
Learn MoreIf you are experiencing issues with the comparison tool, please disable your adblocker.
Nidec
High efficiency induction motor.
Hub Highlights:
- Low noise
- High efficiency at full speed
- Compatible with more types of VFDs
Last Edited on: March 31, 2023
Model Number | SY068 |
Type | Induction |
Frame | 213T |
Horsepower (HP) | 7.5 |
RPM | 1765 |
Phase | 3 |
Voltage | 200VAC |
Last Edited on: March 31, 2023
Drive Manufacturer | Schneider |
Drive Model Number | ATV930 D11M3 |
Date of Test | Jun-22 |
Testing Results: | "System" includes the motor drive and motor itself. Airflow test points were chosen to assist users estimate fan energy savings in HVAC equipment. See picture for full results. Tests accurate within ±0.2% |
System Efficiency at 100% Airflow | 86.4% |
System Efficiency at 90% Airflow | 85.9% |
System Efficiency at 80% Airflow | 84.6% |
System Efficiency at 65% Airflow | 80.4% |
System Efficiency at 50% Airflow | 72.1% |
System Efficiency at 30% Airflow | 42.6% |
Motor Efficiency at 100% Airflow | 90.4% |
Motor Efficiency at 90% Airflow | 90.2% |
Motor Efficiency at 80% Airflow | 89.7% |
Motor Efficiency at 65% Airflow | 87.9% |
Motor Efficiency at 50% Airflow | 83.3% |
Motor Efficiency at 30% Airflow | 62.3% |