Testo 160 IAQ
CO2 sensors are used to control ventilation systems and monitor indoor air quality. They can be stand-alone sensors or integrated into thermostats or air quality monitoring platforms.
Learn MoreIf you are experiencing issues with the comparison tool, please disable your adblocker.
Testo 160 IAQ
The Testo 160 IAQ is a carbon dioxide, temperature, atmospheric pressure, and humidity sensor with a display that can be used for long-term monitoring.
Hub Highlights:
- Basic display of CO2 and temperature values
- No building automation system connection. Web-based software displays historical data via graphs and has configurable alarms
- Excellent performance on Hub CO2 accuracy testing protocols
- Includes temperature, humidity, and pressure sensors. Requires Wi-Fi connectivity to view and configure devices
Last Edited on: Sep 30, 2021
Model Number | 160 IAQ |
Last Updated | 8/3/2021 |
Sensor Type | Non-dispersive infrared (NDIR) Manufacturer: Unknown |
Power Input | 5 VDC |
Outputs | Testo Cloud interface |
Altitude Correction Method | Automatic via pressure sensor |
Measurement Range | 0-5000 ppm |
Reported Accuracy | Battery Power: ± (50 ppm + 3% of reading) With external power supply: ± (100 ppm + 3% of reading) |
Display of C02 Value | On device and Web (account required) |
Uses Automatic Background Calibration (ABC) | No |
Last Edited on: Sep 30, 2021
Model | 160 IAQ |
Date of Test (including warm-up period if device uses automatic background calibration) | Jun 16,2021 - July 20, 2021 |
Sample Size | 5 |
Error of CO2 measurement @1100 ppm (average) (ppm)
|
15.9 |
Error of CO2 measurement @ 1100 ppm (standard deviation) (ppm)
|
19 |
Accuracy Metric
|
<±75ppm |
Noise of CO2 measurement @1100 ppm (Average) (ppm)
|
7.4 |
CO2 Full results
|
See Box Plot |
Operating Power for Sensor (watts) | 0.23 |
Operating Power for Gateway (watts) | N/A |
Operating Power for Sensor + Gateway (watts)
|
0.23 |
Operating Power Metric
|
<±0.5 W |
Maximum Number of Sensors per Gateway | N/A |
Last Edited on: Sep 30, 2021
Data Source: Staff at the UC Davis Western Cooling Efficiency Center
User Interface
Can the sensor display the CO2 level to occupants? If yes describe.
Yes - Display on the sensor
User Interface
Can the sensor display a visual indicator to occupants that the CO2 level has exceeded a programmed threshold? If yes, describe (what does the indicator look like, what the default thresholds are, and can the threshold be changed).
Yes - the air quality is displayed with traffic light style green, yellow, and red LED notifications (The threshold for yellow and red is set through the web interface )
Reporting Capabilities
Can the sensor alert facilities (such as an email, text, or call phone application) when the CO2 level has exceeded a programmed threshold? If yes, describe (what does the indicator look like and can the threshold be changed).
Yes - The facilities dashboard can be used to configure alerts for elevated CO2 levels that are then sent by text or email
Reporting Capabilities, Integration Capabilities
How can the CO2 sensor data be logged? If proprietary software, describe (what type of account is needed, what logging intervals are available, what does it look like, and describe its capabilities including data download capabilities).
Wi-Fi with proprietary software. An advanced account is needed to adjust the logging interval. Data can be downloaded to a CSV file or pdf.
Integration Capabilities
Can the CO2 sensor interface with a building automation system (BAS) or demand control ventilation (DCV) system controller? If yes, describe if integration capabilities are vendor specific.
No
Integration Capabilities
If sensor can interface with a BAS or DCV system controller, is additional hardware required?
No
Installation
Does the sensor require specialized software for installation? If yes, describe
No
Installation
Does the sensor require specialized training for installation? If yes, describe
Yes, assistance connecting to the web interface may be needed
Operation
Does the sensor require on-going maintenance? If yes, describe
No
Operation
Does the sensor require service contracts for ongoing data access? If yes, describe
Yes - The account option enabling advanced settings is subscription-based