Talosys NB307-915M
CO2 sensors are used to control ventilation systems and monitor indoor air quality. They can be stand-alone sensors or integrated into thermostats or air quality monitoring platforms.
Learn MoreIf you are experiencing issues with the comparison tool, please disable your adblocker.
Talosys NB307-915M
Indoor air quality monitoring platform with CO2 sensors with web-portal for long-term monitoring.
Hub Highlights:
- CO2 value displayed on device and web-portal.
- No building automation system connection. Dashbaord displays historical data via graphs and has configurable alarms.
- Excellent performance on Hub CO2 accuracy testing protocols
- Includes CO2, temperature, humdity, and other sensors
Last Edited on: 12/11/2023
Sensor Type | Non-dispersive infrared (NDIR) Manufacturer: Senseair |
Power Input | 5 VDC |
Outputs | Wifi to cloud-based interface (requires gateway) |
Altitude Correction Method | Programmable through app |
Measurement Range | 400-2,000 ppm with specified accuracy, up to 10000 ppm |
Reported Accuracy | ± (70 ppm + 3% of reading) |
Display of C02 Value | On device and web (account required) |
Uses Automatic Background Calibration (ABC) | Yes |
Model | NB307-915M |
Date of Test | August 8-9, 2023 |
Sample Size | 5 |
Error of CO2 measurement @1100 ppm (average) (ppm)
|
-31.4 |
Error of CO2 measurement @ 1100 ppm (standard deviation) (ppm)
|
3.59 |
Accuracy Metric
|
less than ±75ppm |
Noise of CO2 measurement @1100 ppm (Average) (ppm)
|
2.04 |
CO2 Full results
|
See Box Plot |
Operating Power for Sensor (watts) | 0.039 |
Operating Power for Gateway (watts) | 3.24 |
Operating Power for Sensor + Gateway (watts)
|
0.071 |
Operating Power Metric
|
less than ±0.5 W |
Maximum Number of Sensors per Gateway | 100 |