Distech Controls Eclypse
Historically, a Building Automation System (BAS) adds monitoring and control features to heating, ventilation, and cooling (HVAC) systems. Today, some BASs can also integrate with other building systems such as lighting, blinds, security, fire, etc. These BASs can be used to save energy by allowing users to monitor system parameters, identify faults, and implement schedules/programs.
Learn More
The Distech Controls Eclypse Building Automation System solution consists of the EC-Gfx programming software and a range of other programs, building controllers, general controllers, and application specific controllers. This programable system integrates with HVAC and other building systems using a combination of open communication protocols and proprietary protocols.
- BACnet (IP & MS/TP), Modbus (TCP/IP & RTU), Wi-Fi communication options between ECY-S1000 building controller and lower-level controllers
- Free software with no limitations on number of control points, buildings, etc. (includes: EC-Gfx, Eclipse designer, Xpressgfx, Builder, my DC control application, Eclipse commissioning)
- Free software with no limitations on number of control points, buildings, etc. (includes: EC-Gfx, Eclipse designer, Xpressgfx, Builder, my DC control application, Eclipse commissioning) RESTful Application Programming Interface (API)
- Manufacturer advertised Automated Demand Response (ADR)
- Cyber security includes FIPS 140-2
Product Name | Eclypse |
Communication protocols - from building controller to other controllers | BACnet (IP & MS/TP), Modbus (TCP/IP & RTU), Subnet-Ethernet, M-Bus, Bluetooth, Wi-Fi (requires adapter), EnOcean (requires adapter) |
Software - steps for system setup |
1) Software Center - for installation/updating software, 2) xpressNetwork Utility - interface to configure connection settings for ECY products, 3) EC-gfx - software for programming controllers, 4) Other optional software includes: Xpressgfx , Builder, my DC, control application, Eclipse commissioning, VEXX. |
Programming options | Programmable and/or built-in application specific programs |
Software licensing and software agreement (SMA) | No initial cost or update costs for most software (EC-Gfx, Eclipse designer, Xpressgfx, Builder, my DC control application, Eclipse commissioning). VEXX has an initial cost per controller for factory uploaded custom control programs. |
Software licensing structure | Software has no limitation on number of control points, buildings, etc. (includes the following software: EC-Gfx, Eclipse designer, Xpressgfx, Builder, my DC control application, Eclipse commissioning). |
User interface style | Graphical programming with graphical dashboards available |
User interface connection options | Central PC, computer on network, web interface and phone application (myDC Control and/or myDC AirBalancing) |
Dashboards | Yes, with ECLYPSE Designer (previously xpressENVYSION) |
Remote access | Yes, with optional ENVYSION package |
Different user permissions | Yes |
Cyber security features | User passwords, auto log-off, and FIPS 140-2 |
Building controller built-in I/O terminals (connection locations) | None, but can connect to I/O modules |
Building controller maximum expansion modules or I/O modules that add multiple terminals (connection locations) | (20) I/O modules |
Installation approach | Authorized integrators |
Manufacturer training | Yes, online training modules/courses to learn about the software, controllers and system |
Service contract | Yes, optional through system integrator |
System application | New construction & retrofit |
Monitoring and trending | Yes |
Report output type | Excel |
Export point data and trends (SQL) | Yes |
Setpoint recording | Yes |
Alarm/fault detection | Yes |
Wireless capabilities | Yes, Wi-Fi for controllers with Eclypse Wi-Fi adapter add-on and Bluetooth or EnOcean to application specific controllers with Open-To-Wireless™ Adapter |
Manufacturer advertised variable air volume (VAV) controller with integrated actuator | Yes, ECY-VAV |
Manufacturer advertised thermostats | Yes |
Manufacturer advertised blinds controller | Yes |
Manufacturer advertised display monitor device | Yes |
Manufacturer integrated application programming interface (API) | Yes, RESTful API |
Manufacturer integrated automated demand response (ADR) | Yes |
Warranty (yrs.) | 2 years |
Date of Test | 12/06/21 - 08/30/23 |
Model | ECY-S1000-28-MS, ECY-PS24, ECY-8UI6UO-HOA, ECY-8UI6DOT-HOA, ECY-303-M3, ECY-TU-203-IMP, ECY-VAV-IMP, EC-Smart-Vue-CHM |
Sample Size | 1 |
Average (and maximum) power consumption of a BAS when controlling building HVAC loads per square foot (mW/sf) of California building space
|
2.86 (16.6) |
Average (and maximum) power consumption of a BAS when not controlling building HVAC loads (standby mode) per square foot (mW/sf) of California building space
|
1.90 (12.2) |
Average (and maximum) energy consumption per square foot per year (Wh/sf/yr) of California building space for a BAS
|
32.9 (193) |
Power failure recovery after 10 seconds (Yes or No)
|
Yes |
Power failure recovery after 112 minutes (Yes or No)
|
Yes |
Average time (and maximum time) in seconds (s) for the software to update the temperature setpoint as a result of the user manually overriding values via the software
|
0.8 (1.2) |
Average time (and maximum time) in seconds (s) for the software to update the temperature setpoint as a result of the user manually overriding values via the thermostat
|
4.9 (8.4) |
Average time (and maximum time) in seconds (s) for the software to update the temperature setpoint as a result of the user manually overriding values via a scheduled setpoint change
|
17.0 (17.3) |