Cooper Wavelinx Lite Ambient integrated
Luminaire-integrated Controls (LIC) are lighting systems in which sensors, control logic, and dimming capability are embedded directly within each luminaire. LICs enable core energy-saving strategies, such as occupancy sensing, daylight harvesting, and high-end trim, without requiring external sensors, low-voltage control wiring, or centralized network hardware. Fixtures can also communicate locally to operate in coordinated groups.
Learn More
A simplified wireless lighting control system that uses a Bluetooth mesh network to enable occupancy and daylighting control without gateways or servers. Devices can be grouped and commissioned via a mobile app; the system supports basic control features (on/off, dimming, daylight response), making it suitable for smaller scopes or retrofit spaces.
- 5 or 10 Year Warranty
- App-based commissioning
| Model Number | 22CZ2 32 UNV L835 HCD1 WAB |
| Nominal Voltage for Connected Luminaire | 120/277/347 VAC |
| Sensor Dimensions | Circular, 32 mm diameter |
| Max Number of Connected Nodes | 50 |
| Max Zones per Area | 16 |
| Connectivity Method between Sensors | Bluetooth |
| Network Connectivity | Unspecified |
| Control Methods | Occupancy, Daylight Harvesting, High End Trim, Luminaire Level Lighting Control |
| Sensing Methods | Daylighting, Occupancy |
| Occupancy Sensor Type | Passive Infrared |
| BACnet Capable | Unspecified |
| Rest API | Unspecified |
| Operating Temp | 0 C - 55 C |
| Operating Environment | Indoor |
| Standards/Certifications | cULus Listed, DLC listed, FCC |
| Sample Size | 1-3 |
|
Power Consumption for LIC (LED Disconnected)
|
0.281 |
|
Power Consumption (W) for LED (LIC Disconnected)
|
25.5903 |
|
Power Consumption (W) for LIC (Factory Default)
|
0.2822 |
|
Power Consumption (W) for Luminaire (Factory Default)
|
25.6451 |
|
Power Consumption (W) for LIC (Commissioned)
|
0.2894 |
|
Power Consumption (W) for Luminaire (Commissioned)
|
25.6045 |
|
Power Consumption (W) for LIC (Networked)
|
0.2855 |
|
Power Consumption (W) for Luminaire (Networked)
|
0.3647 |
|
Daylight Saturation Point (fc)
|
112.80 |
|
Setpoint variance during daylight increase (fc)
|
3.70 |
|
Setpoint variance during daylight decrease (fc)
|
3.50 |
|
Occupancy Major Motion Response
|
Passed (see chart) |
|
Occupancy Minor Motion Response
|
Passed (see chart) |