nLight AIR integrated
Luminaire-integrated Controls (LIC) are lighting systems in which sensors, control logic, and dimming capability are embedded directly within each luminaire. LICs enable core energy-saving strategies, such as occupancy sensing, daylight harvesting, and high-end trim, without requiring external sensors, low-voltage control wiring, or centralized network hardware. Fixtures can also communicate locally to operate in coordinated groups.
Learn More
A wireless, app-configurable lighting control platform that provide control via 900 MHz RF connectivity, eliminating the need for new low-voltage wiring. It enables occupancy sensing, daylight-based dimming, and scheduling across luminaires using embedded or compatible sensors, useful where wireless networking is preferred or retrofit wiring is impractical.
- 5 Year Warranty
- Integratable with enterprise level NLC offerings
- App-based commissioning
- Offers dual sensing occupancy technology (PIR and Michrophonics)
| Manufacturer | Acuity |
| Model Number | STAK 2X2 3000LM 80CRI 35K COL Min1 MVOLT NLTAIR2 APIR |
| Nominal Voltage for Connected Luminaire | 120/277/347 VAC |
| Sensor Dimensions | Circular, 33 mm diameter |
| Max Number of Connected Nodes | 128 |
| Max Zones per Area | Unspecified |
| Connectivity Method between Sensors | Wireless 900 MHz |
| Network Connectivity | Network Connectivity supported only with Gateway integration |
| Control Methods | Occupancy, Daylight Harvesting, High End Trim, Luminaire Level Lighting Control, Scheduling (with gateway) |
| Sensing Methods | Daylighting, Occupancy |
| Occupancy Sensor Type | Passive Infrared and/or Michrophonics |
| BACnet Capable | When integrated to larger nLight offering |
| Rest API | When integrated to larger nLight offering |
| Operating Temp | Unspecified |
| Operating Environment | Indoor |
| Standards/Certifications | DLC listed, FCC |
| Sample Size | 1-3 |
|
Power Consumption for LIC (LED Disconnected)
|
0.1217 |
|
Power Consumption (W) for LED (LIC Disconnected)
|
24.0466 |
|
Power Consumption (W) for LIC (Factory Default)
|
0.0715 |
|
Power Consumption (W) for Luminaire (Factory Default)
|
9.2995 |
|
Power Consumption (W) for LIC (Commissioned)
|
0.1238 |
|
Power Consumption (W) for Luminaire (Commissioned)
|
24.3059 |
|
Power Consumption (W) for LIC (Networked)
|
0.1231 |
|
Power Consumption (W) for Luminaire (Networked)
|
1.2115 |
|
Daylight Saturation Point (fc)
|
465.50 |
|
Setpoint variance during daylight increase (fc)
|
286.00 |
|
Setpoint variance during daylight decrease (fc)
|
260.00 |
|
Occupancy Major Motion Response
|
Passed (see chart) |
|
Occupancy Minor Motion Response
|
Passed (see chart) |